|
Chilled-Water
Systems for Cooling
After
packaged equipment, chilled-water systems are the most common
air-conditioning systems in U.S. commercial buildings, and
they predominate in large buildings. Each system includes
refrigerant, air, and water loops, and each loop has a circulation
device (pump, fan, or compressor). The components of a chilled-water
system include a chiller, air-handling units with chilled-water
coils, chilled-water loop(s) with chilled-water pump(s), a
condenser water loop, condenser water pump(s), and a cooling
tower. Optimizing chilled-water systems requires careful integration
of these components. The chiller packages a compressor with
water-to-refrigerant heat exchangers (evaporator and condenser).
It is the heart of the system (and generally the single largest
energy user). However, simply selecting a high-efficiency
chiller does not guarantee high performance.
Over
the past two decades or so, the constraints and opportunities
for chilled-water systems have changed dramatically, opening
new opportunities for greatly increased efficiency.
- Mandatory
phase-out of CFC refrigerants such as R-11 and R-12 has
forced users to consider refrigerant or chiller replacement.
As of early 2004, roughly half the CFC-using chillers had
been converted or replaced with units using other refrigerants
(Air-Conditioning and Refrigeration Institute. 2003. "Economy
Affects CFC Chiller Phaseout." Press Release. Arlington,
Va.: Air-Conditioning and Refrigeration Institute). If nothing
else is done, this can have a negative impact on efficiency.
- Manufacturers
have improved the efficiency of their top-end chillers by
about 40 percent, offering dramatic reductions in energy
use and peak demand.
- New
design tools, such as DOE-2, EnergyPlus, and enhanced versions
of Carrier's HAP and Trane's Trace, have improved the ability
of designers to understand both peak loads and annual energy
use, giving new emphasis to specifying equipment with high
part-load efficiency.
- Cost-effective
variable speed drives (VSDs) are being applied to pumps,
fans, and the chillers themselves, greatly improving part-load
efficiency and minimizing the inefficiencies associated
with oversized equipment.
- Advanced
controls allow closed-loop feedback to optimize many more
variables than earlier systems could accommodate. Using
new sensors and VSDs, controls can now optimize approach
temperatures, air-side (and occasionally water-side) economizers,
and air delivery.
- New
air distribution systems are emerging. Under-floor air distribution
(UFAD) may account for 10 percent of large office construction
today, and dedicated outdoor air systems (DOAS) are gaining
popularity, too. Both promise greater comfort and lower
energy costs, and both may reduce capital costs with good
designs.
These
changes illustrate why chilled-water system design requires
an experienced engineer. Traditionally, the engineer estimated
or calculated the building load (peak demand), and selected
equipment to serve that load. Today, the optimal process differs
and should include the following steps amplified from unpublished
EPA working papers).
First,
peak demand remains very important since so many utilities
impose demand charges or time-of-day rates. The demand portion
of the electric bill is often roughly the same size as the
energy portion. To limit demand charges, the design team should
reduce loads wherever it can be done cost-effectively. For
example, up-to-date lighting is generally very profitable
for both new construction and retrofits. As noted in Chapter
2, modern lighting systems can save 50 to 80 percent of
lighting energy (Advanced
Lighting Guidelines. EPRI TR-101022s, Revision I.
Palo Alto, Calif.: Electric Power Research Institute). Well-designed
systems should satisfy needs while using 1 watt/ft2 or less.
Similarly, HVAC "parasitics," the energy and peak
demand of system fans and pumps, can rival the chiller's demand.
Thus, proper sizing of ducts, fans, piping, and pumps can
substantially reduce the size of the motors required. This
reduces component costs. Since the engineered design leads
to smaller equipment at peak loads, this also means that variable
speed drives (below) are more likely to operate where they
are most efficient.
Second,
part-load efficiency is just as critical for almost all buildings.
Designing for part-load efficiency requires comprehensive
energy analyses. Again, the building's "parasitics"
(the energy use by pumps, fans, and other auxiliary equipment)
are generally rich lodes of potential savings through proper
pipe and duct sizing (to reduce pressure-related losses) and
proper motor selection. For example, a heat recovery wheel
with very high pressure drops may require more (fan) energy
at part loads than it saves, and thus must be equipped with
a bypass if it is to be used cost-effectively.
This
leads to a third guideline: think about the system, not just
the components.
- Variable
speed drives improve part-load efficiency with low peak-load
penalties (indeed, since pumps are almost always substantially
oversized, variable speed drives almost never run at full
speed, so very few ever see penalties from the drive electronics).
- Consider
combining variable speed drives with primary-only water
loops using two-way valves on cooling coils. Primary-only
pump strategies deliver chilled water directly from the
chilled-water pump to the terminal equipment, rather than
using hierarchic secondary (or even tertiary) loops for
pressure control. Modern chillers are much more tolerant
of variable water flow rates and inlet temperatures.
- Select
cooling coils for high temperature drops at design conditions
to reduce pumping energy.
- Cooling
tower capacity is much less expensive than chiller capacity.
A larger tower will provide cooler water to the chiller
at very low cost and thus improve its efficiency at "off-design"
conditions. Propeller fans are much more efficient than
centrifugal ones and should be selected when possible. Two-speed
or "pony" motor systems give almost all of the
benefits of variable speed drives for cooling tower fans,
at much lower cost.
- Modern
energy management systems are much more sophisticated and
able to optimize performance. They allow simultaneous protection
of equipment and maximum energy efficiency and are mandatory
for complex chiller-based systems.
- In
some cases, heat recovery ventilation or energy recovery
(enthalpy) equipment will be cost-effective, typically by
reducing the temperature and/or humidity of the outside
air introduced for ventilation. It is important to evaluate
this equipment both for its peak-load reduction capability
and for the impact on part-load efficiencies: some designs
have very high pressure losses, requiring large amounts
of fan energy even at part load.
Thus,
a healthy dose of system analysis is likely to pay huge demands.
This starts with agreements among the design team on the loads
to be met, after taking advantage of all appropriate ways
to reduce them. It next requires a detailed load simulation
to compute hourly loads for the design year. This has two
virtues: (1) it allows comparison of the impacts of design
changes, such as loads, approach temperatures, and the effects
of adding variable speed drives or more efficient chillers;
and (2) the resulting load profiles are also required as inputs
to a bid package for chiller manufacturers to design or select
the most appropriate chiller(s) for the application.
After
following all these steps, you can generally choose a smaller,
more efficient chiller with a larger than normal cooling tower
to get an efficient, well-functioning system.
Selecting
the right chiller. The type of chiller used in any given
application is often determined by the desired cooling capacity
(tons), product or manufacturer preference, and the viability
of a chilled-water system for the application. Other considerations
include footprint, weight, and availability. From an energy
viewpoint there are three critical selection criteria: the
type of condenser (air- or water-cooled), the type of compressor,
and the unloading mechanism.
In the
United States, built-up chiller systems are water-cooled.
In addition to its core functions, the chilled-water loop
can be quite useful for other loads such as water-cooled air
conditioners for computer or electric equipment rooms. The
condenser loop (serving the cooling tower) also provides a
low-cost resource for heat-recovery water heating. The major
reservations about chilled-water systems are higher first
cost and cooling tower issues. In many projects, concerns
about siting the cooling tower (physical appearance, biochemical
control, water drift and risk of entraining condenser mist
at air inlets, and noise) are the leading factors that discourage
selection of water-cooled systems.
Four
technologies dominate the electrical chiller market: reciprocating,
scroll, screw, and centrifugal compressors. Each type has
a size range where it is most cost-competitive. In general,
centrifugal chillers are the most efficient both at full and
part loads and reciprocating are the least efficient. In general,
smaller chillers (less than 100 tons) are either reciprocating,
screw, or scroll. Screw compressors generally range in size
from 10 to 1,100 tons but are most common in the 100 to 300
ton range. In sizes above 300 tons, centrifugal compressors,
which range from 70 to 9,000 tons, are generally more cost-effective.
Each
chiller type has a unique mechanism for varying capacity with
demand ("unloading"), which can substantially affect
part-load performance. Reciprocating and scroll machines use
multiple compressors to provide stages of cooling capacity.
However, cycling compressors on and off results in relatively
unstable chilled-water temperatures and is the least efficient
of the unloading mechanisms. Screw machines use a slide valve
for unloading, and centrifugal compressors use inlet vanes.
Variable speed drives are the most effective means of varying
capacity with demand for these types, and are increasingly
specified.
Centrifugal
chillers offer buyers the most flexibility in terms of full-
and part-load efficiency. They come in a wide range of sizes
and are typically engineered to the users' specifications
from a range of shells, tube configurations, impellers, gears,
and motors. Careful selection of a centrifugal machine can
provide optimal performance as it can be designed to closely
match the plant profile. Multiple-stage centrifugal chillers
can also be appropriately applied for applications dominated
by other compressor types (such as applications with low supply
temperatures or high lifts encountered in thermal storage,
low temperature air, or heat recovery systems).
Chiller
performance ratings. Chillers are specified by their design
capacity in tons (1 ton = 12,000 Btuh) and their design efficiency
in kW/ton. ASHRAE Standard
90.1 establishes minimum energy efficiency levels. The
New Buildings Institute has developed more stringent recommendations
that provide increased energy and operating cost savings.
These are contained in the table below.
Recommended
Chiller Performance Levels


Cooling
tower selection. In water-cooled systems, the cooling
tower selection is the Achilles heel of the central plant.
Cooling tower capacity is purchased at one-tenth to one-twentieth
of the installed cost of chillers, yet it is often limited
to the bare minimum required to get the job done. This
is an unfortunate economic choice when you consider that
a larger cooling tower can reduce chilled-water plant
operating costs by 10 to 20 percent. In selecting a cooling
tower, the following should be considered."
Propeller fans on average use 50 percent of the energy
of centrifugal fans.
-
For
motors above 5 hp, always use two-speed or pony motors
(e.g., one large and one small motor); adjustable or
variable speed drives (VSDs) will provide negligible
savings over two-speed or pony motors. VSDs will provide
tighter control of the condenser water temperature,
which may be valuable with some control schemes, or
required if the tower is serving sensitive equipment.
-
Approach
temperature optimization should be done by evaluating
towers at several possible approaches including a 3ºF
to 5ºF low-approach selection.
-
Optimizing
controls can save money (see section on HVAC
Controls).
Installation.
Manufacturers of chillers and towers provide detailed
information for proper installation and start-up of
their equipment. These instructions should be followed
carefully. Note that it is critical to provide adequate
clearances around central plant equipment for proper
maintenance. Recommended clearances are provided in
manufacturer literature.
For
cooling towers, in addition to the clearances for
maintaining fans and pumps, space must be provided
to ensure adequate airflow through the tower and prevent
crossover from the tower discharge to the inlets.
Tower water can be corrosive and tower discharge plumes
must be located so that they will not damage building
finishes or automobiles in adjacent parking lots.
In all cases, extreme care should be taken to prevent
tower discharge from entering the building through
ventilation inlets.
Completion
(Commissioning) Requirements
Of
prime importance to successful long-term energy efficiency
are the steps taken at the time of project completion
to assure that the chiller system is working properly
and that an orderly transition occurs from the contractor
to the owner. Steps include start-up and testing all
equipment; testing, adjustment, and balancing (TAB)
reports; "as-built" drawings with narrative
descriptions of the systems; owner training; and complete
operation and maintenance (O&M) manuals. In addition
to the traditional activities to document the design
and installation, performance tests will assure that
equipment and controls are installed and operating
as designed. (For a more thorough description of the
commissioning process, see Portland Energy Conservation,
Inc. and Oak Ridge National Laboratory. 1999. A
Practical Guide for Commissioning Existing Buildings.
ORNL/TM-1999/34. Portland, Oreg.: Portland Energy
Conservation, Inc. and Oak Ridge, Tenn.: Oak Ridge
National Laboratory.
Maintaining
the chiller system. Maintenance activities in
a chilled-water plant fall into the following categories:
avoiding and reducing scale on the heat exchanger
surfaces; avoiding fouling from biological growth
and debris on the condenser water systems; lubricating
moving parts; maintaining the calibration of critical
sensors; and checking and maintaining the refrigerant
charge. These activities require specialized training
and procedures in many cases, and are frequently outsourced
to firms that focus on these businesses.
Central
Heating Plants: Boilers and Furnaces
Boilers
and furnaces form the heart ofthe
heating system for many commercial buildings. Boilers
account for more than 40 percent of the heating energy
in commercial buildings with furnaces comprising an
additional 30 percent. Furnaces are largely restricted
to smaller buildings. Boilers supply steam or hot
water to a hydronic distribution system (often through
hot water coils in the same air handlers as the chilled-water
coils), whereas furnaces warm air that is then distributed
either directly to a space (as with vertical air turnover
furnaces) or through an air distribution system.
Rating
energy efficiency. The efficiency with which these
boilers and furnaces convert fuel energy (either from
combustible fuels, such as oil and gas, or from electricity)
is measured differently for different equipment types.
Thermal
efficiency (TE) is a steady-state measure. It measures
energy delivered to the system, net of flue and jacket
losses, but it does not include the effects of heat
loss due to cycling during off-design conditions (similar
to EER). It is used to rate large commercial boilers
(>= 300,000 Btuh and <=2,500,000 Btuh).Combustion
efficiency (EC) is the steady-state percentage of
fuel that is combusted minus the energy that goes
up the flue. Thus, it treats jacket losses as useful
work, and does not include cycling losses. Since combustion
efficiency does not include shell losses, its value
is typically at least 2 percent higher than thermal
efficiency for the same unit.
Design
factors and energy efficiency. Fuel combustion
efficiency sets the upper limit to heating system
efficiency. Broadly speaking, two recommended classes
are available: power-vented non-condensing and condensing.
The former typically show steady-state efficiencies
above about 75 percent, while the latter range from
about 90 to 96 percent. Offsetting their higher efficiency,
condensing units cost more to purchase and require
safe disposal of the acidic condensate (typically
to the sanitary sewer). The efficiency boost comes
from recovering heat in the flue exhaust gas. Therefore,
one highly cost-effective strategy is to team one
condensing boiler with one or more non-condensing
units. The condensing unit is the "lead"
boiler in the train, often operating year-around.
This requires outdoor reset or similar control strategies
to improve efficiency by reducing supply and return
temperatures when demands are low. Alternatively,
the condensing boiler can be used to preheat the entering
or return water for conventional boilers for an overall
increase in plant efficiency.
Distribution
system and standby losses also significantly affect
heating system efficiency. Boilers tend to have lower
steady-state efficiencies than furnaces but higher
overall system efficiencies, since hydronic distribution
systems are inherently more efficient than air distribution
systems. Well-sealed duct runs and duct insulation
improve furnace distribution system efficiency.
Recommendations
for purchasers. When purchasing a new boiler,
choose a high-efficiency unit. For all but the smallest
installations, an evaluation by an experienced engineer
is likely to be cost-effective, since it allows for
"right-sizing" the unit and using the savings
from not oversizing to pay for improvements to the
efficiency of the unit or distribution system and
controls. Retiring older boilers or furnaces in favor
of high-efficiency alternatives is generally cost-effective
for all but the smallest commercial buildings. When
replacement isn't cost-effective, consider replacing
the burner with a power burner or at least adding
vent dampers. Also evaluate the benefits of adding
smaller boilers or furnaces to provide part-load heating.
For example, a high-efficiency packaged boiler sized
for average mild weather loads can be installed in
parallel with a large existing boiler sized for peak
loads. The large boiler then operates only when the
front-end packaged unit cannot meet the load, resulting
in a higher seasonal efficiency. The following tables
illustrate two approaches to very high-efficiency
boilers. The first table is a list developed by ACEEE
that shows the highest performance levels for which
there is significant competition in the market. The
second table, based on economic screening, was prepared
by the New Buildings Institute as a guide to cost-effective
high performance equipment. Where boilers are used
heavily (very cold winters) and/or fuel prices are
very high, the ACEEE list may be preferable; otherwise
the NBI recommendations give good guidance.
ACEEE
Recommendations for Highest-Efficiency Boilers >
300,000 Btuh
Integrating
water heating. In many commercial buildings, the main
boiler is used both for space conditioning and water
heating. Particularly when domestic hot water is generated
by the primary heating boiler and uses a "hotel"
loop to circulate hot water continuously, the system
will have low efficiency because of the high pumping
energy and radiative losses from the loop. A smaller
packaged condensing boiler sized for shoulder-season
space loads can also provide service water during
mild weather, largely eliminating the standby losses
of the primary boiler. Beyond this, in schools and
office buildings with small hot water loads, distributed
demand or small storage water heaters may be more
efficient. This will be particularly true if heat
pump water heaters can be employed, using toilet room
exhaust for the heat source.
Heating
equipment maintenance. A variety of maintenance activities,
particularly for the combustion system, should be
undertaken annually. Critical adjustments are needed
to ensure maximum steady-state efficiency as well
as safe combustion conditions, which can be determined
by flue gas analysis. Although routine cleaning and
"tune-ups" of boilers and furnaces do not
necessarily bring energy savings, they are part of
good maintenance practice, especially for oil-fired
systems. For boiler tune-ups to achieve energy savings,
selecting the right candidate boilers for a "high-efficiency"
tune-up is as important as having a properly trained
and equipped technician. Older coal boilers converted
to gas have been found to be good candidates for tune-ups.
High oxygen (O2) readings and high stack
temperatures indicate potential savings from reducing
excess air. On the other hand, tune-ups of gas boilers
have shown marginal savings at best. In all cases,
testing and adjustment must be conducted under actual
operating conditions. With properly trained technicians
and screening of candidate boilers, tune-ups yield
cost-effective savings.
|